App-37
Appendix-1 Parameter List
Appendix
Control parameter
H001
Auto-tuning selection
[Auto-tuning select]
00: OFF (Disabled)
01: ON (STOP)
02: ON (Rotation)
00 No 4-111
H002
Motor parameter
selection
[Motor data select]
00: Standard motor parameter
01: Auto-tuning parameter
02: Auto-tuning parameter
(online auto-tuning enabled)
00
No
4-111
4-113
4-115
H202
* 2nd motor
parameter selection
[Motor data select-
M2]
00
H003
Motor capacity
selection
[Motor capacity]
0.20 to 160.0
Factory
default
No kW
4-19
4-111
4-115
4-118
H203
* 2nd motor capacity
selection
[Motor capacity-M2]
Factory
default
H004
Motor pole number
selection
[Motor poles]
2/4/6/8/10
4
No Pole
H204
* 2nd motor pole
number selection
[Motor poles-M2]
4
H005
Speed response
[M.speed const]
0.001 to 80.000
1.590
Yes
4-89
4-92
H205
* 2nd speed response
[M.speed const-M2]
1.590
H006
Stabilization
parameter
[M.stabil.const]
0 to 255
100
Yes 4-120H206
* 2nd stabilization
parameter
[M.stabil.const-M2]
100
H306
* 3rd stabilization
parameter
[M.stabil.const-M3]
100
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001