3-36
3-9 Parameter List
3
Operation
Others
b050
Selection of non-stop
function at
momentary power
interruption
00: OFF (Disabled)
01: V-Cnst (STOP) (Enabled (deceleration
stop))
02: NS1 (Enabled (without recovery))
03: NS2 (Enabled (with recovery))
00 No
4-60
b051
Starting voltage of
non-stop function at
momentary power
interruption
0.0 to 1000.0
220/
440
No V
b052
Stop deceleration
level of non-stop
function at
momentary power
interruption
0.0 to 1000.0
360/
720
No V
b053
Deceleration time of
non-stop function at
momentary power
interruption
0.01 to 3600.00 1.00 No s
b054
Deceleration starting
width of non-stop
function at
momentary power
interruption
0.00 to 10.00 0.00 No Hz
b055
Proportional gain
setting of non-stop
function at
momentary power
interruption
0.00 to 2.55 0.20 Yes
b056
Integral time setting
of non-stop function
at momentary power
interruption
0.000 to 65.535
0.100
Yes s 4-63
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.