Section 10 Transferring Data 10-3 Data Transfer Using SPMA
NS-Designer Operation Manual
Reference
♦ The node set from the Network Tab Page is fixed at 1. Transfer will not be performed correctly if
another number is set. Be sure to set 1.
R
R
e
e
f
f
e
e
r
r
e
e
n
n
c
c
e
e
3. After completing the settings, establish online connection and transfer the data (e.g., ladder pro-
gram).
The following example shows how to perform settings for transferring data, such as a ladder program,
from CX-Programmer, via a PT connected via Ethernet, to a PLC connected via Controller Link.
Ladder program, etc.
Ethernet
Controller Link
IP Address:
192.168.0.10
IP Address:
192.168.0.22
Node Address: 22
Controller Link Unit’s
Node Address: 5
Network Address: 1
Controller Link Unit’s
Node Address: 4
Controller Link Unit’s
Unit Number: 2
Network Address: 3
Settings on the PT
Perform the following settings with NS-Designer.
1. Select Settings - System Setting – Comm - All on the NS-Designer.
2. Set Controller Link and Ethernet to Enable, click the Controller Link Tab, and make the follow-
ing settings.
Set the network address for Controller
Link communications between the PT
and PLC.
Set the unit number for the PT’s
Controller Link Unit.
10-54