166
Flow Display Data Section 8-3
8-3 Flow Display Data
8-3-1 Overview
This function displays flowing characters at the bottom of the screen. Charac-
ters can be displayed from any screen that meet the conditions.
8-3-2 Creating Flow Displays
Select Flow Display from the PT Menu. The Flow Display Dialog Box will be
displayed.
Number of Mes-
sages
Enter the number of messages to display. The Message Tab
Page will be displayed if any value greater than 1 is entered.
Start Address Set the start address in the PLC to use to specify whether to
display or hide the messages. Starting from this address, a
consecutive number of words corresponding to the number of
messages will be used to specify displaying or hiding the mes-
sages.
Condition Set the condition of the bit to use to display the message. If a
bit in the PLC is in the specified status, the PT will display the
corresponding message.