71
NV Configuration Section 6-1
6-1-3 Default Setting
The default settings for the NV Configuration are given below.
*1 These functions are not supported by the NV3W.
Tab page Item Setting
Basic Setup PLC Model OMRON SYSMAC-CS/CJ/CP Series Host Link
System Memory Area: Word Area D0 to D2
System Memory Area: Bit Area 0 to 2
Communication
Parameters
COM Port: Baud Rate 9,600 bps
COM Port: Data Length 7
COM Port: Stop Bits 1
COM Port: Parity Bit Even
Communication Error Handling: Retry 5 times
Communication Error Handling: Wait time 3 seconds
Transmission Delay 0 ms
PLC Multiple Con-
nection
PLC Multiple Connection No
Auto-paging Auto-paging Off
Start-up Screen Start-up Screen No. 0
Delay 0
Setup 1 Clock PT clock
Clock: Summer Time
*1
Off
Clock: Transfer Outside
*1
Off
Automatic Backlight OFF Off
Key Press Sound Enabled
Battery Error Display
*1
Off
File Compression On
System Menu Language English
Setup of Multi-Language Exchange: Refer to
PLC
Off
Backlight Brightness Setting Off
Setup 2 SD Memory Card Menu: Automatic Display Off
Hold Memory
Holding PLC Memory
*1
Off
Hold NV Internal Memory Value: Data memory Off
Hold NV Internal Memory Value: Internal
Relay
Off
Recipe Use Recipe Off
Alarm History
Record
*1
Not supported.
Line Graphs Record Not supported.
Operation Security
Operation Security Function Available
*1
Off

Table of Contents