EasyManua.ls Logo

Parker AC30 - Page 326

Parker AC30
522 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D-66 Parameter Reference
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
Actual Field Current
0400
Same as PNO 393
x.x
-200.0 to 200.0
%
NEVER
Calculated field, based on the Id current.
Motor Current Percent
0401
Same as PNO 393
x.x
0.0 to 500.0
%
NEVER
This diagnostic shows the level of rms line current being drawn from the drive as a percentage of the rated current of the relevant
motor definition.
Motor Current
0402
Same as PNO 393
x.x
0.0 to 2000.0
A
NEVER
This diagnostic shows the level of rms line current in Amps being drawn from the Drive.
100% Stack Current A
0403
Parameters::Motor Control::Feedbacks
x.x
0.0 to 500.0
A
NEVER
This diagnostic indicates the stack rating in Amps. This reduces as a function of pwm switching frequency.
Stack Current (%)
0404
Parameters::Motor Control::Feedbacks
x.
0 to 500
%
NEVER
Stack current percentage.
Motor Terminal Volts
0405
Same as PNO 393
x.
0 to 1000
V
NEVER
Volts between motor phases in Vrms.
CM Temperature
0406
Same as PNO 393
x.x
-25.0 to 200.0
°C
NEVER
Temperature of Control Module in
o
Centigrade.

Table of Contents

Other manuals for Parker AC30

Related product manuals