4. BASIC OPERATION
IMR02L04-E3
4-41
Continued from the previous page.
Name Symbol Data range
Factory set
value
Function block 50 (F50.01 to F50.14)
Control action
OS
0: Brilliant II PID control (direct action)
1: Brilliant II PID control (reverse action)
2: Brilliant II Heat/Cool PID control
(water cooling)
3: Brilliant II Heat/Cool PID control (air cooling)
4: Brilliant II Heat/Cool PID control
(cooling gain linear type)
5: Brilliant II Position proportioning PID control
(reverse action)
6: Brilliant II Position proportioning PID control
(direct action)
Based on
model code.
When
specifying
FBR input or
Z action
ordering: 5
When initial
setting is not
specifying: 1
Hot/Cold start
PD
0: Hot start 1 2: Cold start
1: Hot start 2 3: Reset start
0
Start determination point
PDA
0 to Input span (The unit is the same as input value.)
3 % of Input span
Action (high) at input error
AOVE
0: Normal control
1: Manipulated output value at input error
0
Action (low) at input error
AUNE
0
Manipulated output value at input
error
PSM
PID contorl:
5.0 to
105.0 %
Heat/Cool PID control: 105.0 to 105.0 %
Actual output values become those restricted by the Output
limiter.
0.0
Control action at Pattern end *
END.P
PID control or Heat/Cool PID control,
Position proportioning PID control (with FBR input):
0: Control continued 1: Control stop
Control action at Pattern end can be operative when using
Output program function.
Position proportioning PID control (When there is no FBR
input or the FBR input is break):
0: Control continued
1: Open-side output OFF, Close-side output OFF
2: Open-side output OFF, Close-side output ON
3: Open-side output ON, Close-side output OFF
0
Intensity factor of Ramp/Soak
stabilizer
RSS.AJ
0.0 to 1.0
0.0: Unused
0.5
OUT1 proportional cycle time *
T1
0.1 to 100.0 seconds
M: Relay contact output T: Triac output
V: Voltage pulse output D: Open collector output
M: 20.0
V/T/D: 2.0
OUT1 minimum ON/OFF time of
proportioning cycle
O1.TM
0 to 1000 ms 0
OUT2 proportional cycle time *
T2
0.1 to 100.0 seconds
M: Relay contact output T: Triac output
V: Voltage pulse output D: Open collector output
M: 20.0
V/T/D: 2.0
When the
OUT2 is not
provided: 2.0
OUT2 minimum ON/OFF time of
proportioning cycle
O2.TM
0 to 1000 ms 0
OUT3 proportional cycle time *
T3
0.1 to 100.0 seconds
V: Voltage pulse output D: Open collector output
V/D: 2.0
When the
OUT3 is not
provided: 2.0
OUT3 minimum ON/OFF time of
proportioning cycle
O3.TM
0 to 1000 ms 0
Function block 52 (F52.01 to F52.07)
AT bias
ATB
Input span to
Input span
(The unit is the same as input value)
0
AT differential gap time
ATHS
0.0 to 100.0 seconds 10.0
AT time signal action
ATTS
0: Time signal OFF
1: Time signal ON
0
* It is not necessary to change the operation mode to the Reset mode (RESET) when setting the parameters. The parameters may
also be set in the Setup setting mode.
Continued on the next page.

Table of Contents

Other manuals for RKC INSTRUMENT PF900

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RKC INSTRUMENT PF900 and is the answer not in the manual?

RKC INSTRUMENT PF900 Specifications

General IconGeneral
BrandRKC INSTRUMENT
ModelPF900
CategoryController
LanguageEnglish

Related product manuals