EasyManua.ls Logo

Satec PM130 PLUS Series - Page 114

Satec PM130 PLUS Series
176 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 5 Configuring the PM130 PLUS Configuring Recorders
PM130 PLUS Powermeter Series_Installation Operation and Manual 114
4. Select the number of season tariffs in your TOU schedule. Add one additional parameter if you
selected to record the Summary (TOU total) registers as well.
5. Select the maximum number of records you want to be recorded in the file assuming that a new
record will be added once a day.
6. Click OK and send your setup to the meter or save to the meter database.
Factory Preset Data Log Files
Conventional Data Log #1
Data log #1 is factory preset for 15-min periodic recording of the standard energy and demand quantities.
You can freely change the list of recorded parameters and the file update rate.
The default list of parameters is shown in the following table.
No.
Parameter
1
kWh import
2
kWh export
3
kW import sliding demand
4
V1 demand
5
V2 demand
6
V3 demand
Periodic recording data is triggered by Setpoint #1 that is linked to the meter clock. To change the periodic
rate at which data is recorded, change the time interval for the MINUTE INTERVAL trigger in Setpoint #1
(see Configuring Alarm/Control Setpoints).
Billing/TOU Profile Data Log #16
Data log #16 is pre-configured for daily billing energy and maximum demand recording for the last 90 days.
It is automatically updated once a day.
See Billing Profile Log File in Appendix E for the file record structure.

Table of Contents

Related product manuals