Mounting and installation of the compact con
trol panels
Installing the fiber optic cable network module
5
140 | 354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
5.15.3.3 Fiber optic cable connection
If the fiber optic cable network module is mounted in the station, then only
one supply must be connected.
In the case of remote installation, the supply must be shielded and made
redundant in accordance with EN 54.
Figure 68: Example of different wirings of the fiber optic cable network module
Designation Description
A
Station with one network module (SAFEDLINK) and external fiber optic cable
network module
B
Station with one network module (SAFEDLINK) and internal fiber optic cable
network module
C
Station with two network modules (SAFEDLINK) and external fiber optic cable
network module
1 Network module (SAFEDLINK), master module
2 Network module (SAFEDLINK), degraded mode module
3 'Power A', supply input A to fiber optic cable network module
4 'Power B', supply input B to fiber optic cable network module (redundant supply)
1
A1/B1 FCnet connection for line '1'
A2/B2 FCnet connection for line '2'
Fiber optic cable connection (RX), optical receiver
Fiber optic cable connection (TX), optical transmitter
FN2006/FN2007
FN2006/FN2007
FN2006/FN2007
Line 1
Line 2
A1
B1
A2
B2
A1
B1
A2
B2
A
1
B
1
A2
B2
A1
B1
A2
B2
A1
B1
C
1
2
Vsys
Vsys
3
4
Vsys
3
Vsys
Vsys
3
4
Line 2
Line 1
Line 1
Line 2
Power A
Power B
Power A
Power B
Power A
Power B
A1
B1
A2
B2
A1
B1
A2
B2
A2
B2
A1
B1