Mounting and installation of the compact control panels
Installing the fiber optic cable network module
5
141 |
354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
Fiber optic cable wiring
The accessible laser radiation is harmless. It corresponds to Laser Class 1 in
accordance with IEC 60825/ANSI Z136.
The fiber optic cable is wired cross-wise:
The optical transmitter (TX) of one device must always be connected
with the optical receiver (RX) of the other device.
Line 1 must always be connected with line 2.
The bending radius of the fiber optic cable must not be less than the
manufacturer's specification (e.g. 10 x external diameter).
Standard (PC) cable termination is sufficient, 8° polish (APC) is not necessary,
but is supported.