EasyManua.ls Logo

Siemens FUS1010 - Page 202

Siemens FUS1010
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
A.2 I/O Connections and Wiring
FUS1010 IP65 NEMA 4X & IP66 NEMA 7
Operating Instructions, 01/2013, A5E02951520-AC
201
Table A- 22 Input/Output Wiring TB2 7ME39400SA00 - Analog Input Module
Pin Color Function Description Wiring/Cable
TB2-1 Black RTD Current High
TB2-2 White RTD Voltage High
TB2-3 Green RTD Voltage Low
TB2-4 Red RTD Current Low
TB2-5 Blue Ground
RTD Temperature measurement T2 or
Channel 1 Tr (Return Temperature)
AWG. 14 - 24 /
1000 Ft max w/o
factory approval
Table A- 23 Input/Output Wiring TB3 and TB4 7ME39400SA00 - Analog Input Module
Pin TB3
Function
TB4 Function Use Description Behaviour Load Wiring
1 AUX. 1 IN AUX. 3 IN Iin1 Input
2 AUX. 1 COM AUX. 3 COM Iin1 Common
3 AUX. 2 IN AUX. 4 IN Iin2 Input
4 AUX. 2 COM AUX. 4 COM Iin2 Common
Analog
current input
referenced
to meter
ground.
4 to 20mA 200Ω 305 meters
(1000 ft.)
Max w/o
factory
approval
Net load is 335 ohms when safety barriers are used.

Table of Contents