50
SITRANS F M
6. Installation of transmitter
Step 2
Take the SENSORPROM
®
memory unit from
the sensor. Mount the SENSORPROM
®
unit in
the wall mounting unit as shown. The text on the
SENSORPROM
®
unit must face towards the
wall bracket.
Mount an earth wire between PE on connection
board and bottom of connection box.
6.2.3
Remote installation -
Wall mounting
(continued)
MAG 6000
Step 3
Mount the connection plate in the terminal box.
Fix the connection plate with the two diagonal
opposite screws.
Fit the coil
B , electrode A , supply C and output
cables
D respectively and tighten the cable
glands to obtain optimum sealing. Please see
the wiring diagram in “Electrical connections”
Step 4
Mount the transmitter on the terminal box.
Caution
Exposing the transmitter
to direct sunlight may
increase the operating
temperature above its
specified limit, and
decrease display visibilty
Attention
When remote mounted, power supply PE wire
must be connected to PE terminal.
Coil cable shield must be connected to SHIELD
terminal.
Use the supplied insulating tube to insulate the
core shield.

Table of Contents

Other manuals for Siemens MAG 5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens MAG 5000 and is the answer not in the manual?

Siemens MAG 5000 Specifications

General IconGeneral
TypeElectromagnetic Flowmeter
Protection ClassIP67
MaterialStainless Steel, Carbon Steel
Power Supply24 V DC, 100-240 V AC
Accuracy±0.2% of flow rate
CommunicationHART, PROFIBUS, Modbus
Enclosure RatingIP67
Ambient Temperature Range-20°C to +60°C
SizesDN 2 to DN 3000
Lining MaterialsPTFE, Hard Rubber
Electrode MaterialsStainless Steel, Hastelloy, Tantalum
Process Temperature-40 to +180 °C (-40 to +356 °F) depending on liner
Process PressureUp to 40 bar (580 psi)
ApprovalsATEX, FM, CSA, IECEx
Flow Velocity Range0 to 12 m/s
Output Signals4-20 mA, Pulse, Frequency

Related product manuals