EasyManuals Logo

Siemens MAG 5000 User Manual

Siemens MAG 5000
665 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #237 background imageLoading...
Page #237 background image
7ML19981FB05 MultiRanger 100/200 – INSTRUCTION MANUAL Page 63
mmmmm
Pump Control
When the first ON setpoint is reached, the pumps will start, one by one, until the material
level rate of change is set at the same value or greater than the value in:
P703 – Emptying Indicator (pump down applications)
P702 – Filling Indicator (pump up applications)
Set delay between pump starts using P132 – Pump Start Delay.
Single and Dual Point [MR 200]
Single Point Mode: one pump by rate control available that affects all pumps.
Dual Point Mode: a single pump by rate control can be set up for each of the three
available level points. Set Operation for difference or average (P001 = 4 or 5).
Rotating Pumps by Service Ratio [MR 200]
Prerequisite: Set pump relays to a service ratio value (P111 = 54 or 55).
When more than one pump is assigned a Pump Service Ratio value (in any time units) and a
pump start is required (P112 Relay Setpoint ON), the pump with the fewest running hours (with
respect to the assigned ratio values) starts.
Conversely, when a pump stop is required (113 Relay Setpoint OFF), the pump with the
most running hours (as compared to the assigned ratio values) stops.
Notes:
Set all pump control relay ON and OFF setpoints to the same value
If the level is within 5% of Span (P007) of the OFF setpoint, then the next pump
is not started
Parameter Index Value Description
P122 1 1 These values will start Pump Two 50% of the
time and Pumps One and Three each 25% of
the time.
P122 2 2
P122 3 1
Notes:
The MultiRanger will not sacrifice other pumping strategies to ensure that the
ratio is held true
If the pump relays are set to the same value, then the ratio equals 1:1 and all
pumps are used equally (preset)

Table of Contents

Other manuals for Siemens MAG 5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens MAG 5000 and is the answer not in the manual?

Siemens MAG 5000 Specifications

General IconGeneral
TypeElectromagnetic Flowmeter
Protection ClassIP67
MaterialStainless Steel, Carbon Steel
Power Supply24 V DC, 100-240 V AC
Accuracy±0.2% of flow rate
CommunicationHART, PROFIBUS, Modbus
Enclosure RatingIP67
Ambient Temperature Range-20°C to +60°C
SizesDN 2 to DN 3000
Lining MaterialsPTFE, Hard Rubber
Electrode MaterialsStainless Steel, Hastelloy, Tantalum
Process Temperature-40 to +180 °C (-40 to +356 °F) depending on liner
Process PressureUp to 40 bar (580 psi)
ApprovalsATEX, FM, CSA, IECEx
Flow Velocity Range0 to 12 m/s
Output Signals4-20 mA, Pulse, Frequency