Page 148 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB05
mmmmm
Parameters
Enter the Point Number the mA output is based on. This value depends on whether mA
function (P201) is set as transducer or mA input.
If P201 uses a transducer, this parameter can only be altered if P001 (Operation) is set for
DPD or DPA. The values would be 1 for Single Point applications, 1-2 for Dual Point, or 1-3
for DPD or DPA configurations.
The mA output will be the average of the readings from all in service transducers
assigned to the output. Out of service transducers will be ignored.
If P202 mA Output Allocation End contains the value 0, then only 1 transducer has been
assigned to the milliamp output.
P203 mA Output Value / Transducer
Displays current mA output value for the Point Number.
This displays as an Auxiliary Reading when key is pressed in the RUN mode and
does not include adjustments made using Trim features (P214 / P215).
Independent mA Setpoints (P210 and P211)
Use these features to reference the minimum and/or maximum mA output to any point in
the measurement range.
Primary Index Level
Values Range: 0.000 to 22.00 (view only)
Note: This parameter is applicable only if any mA output has the transducer
Point Number as its input source (see P201 and P202).
P201—mA Function
Settings
Action
Level, Space, or Distance
Enter the material level in Units (P005) or percent of
Span (P007) as referenced to Empty (P006).
Volume [MR 200]
Enter the volume in Max Volume (P051) units or as a per-
cent of Max Volume.
Flow [MR 200]
Enter the flowrate in OCM Max Flow (P604) units or as a
percent of OCM Max Flow.
Head [MR 200]
Enter the head in level units (P005) or percent of Max
Head (P603).
Volume Rate [MR 200]
Enter the volume rate in volume/min. Ensure the % sym-
bol is displayed before attempting to enter a % value.
mA input or
Communications Input
Not Applicable