Page 102 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB05
mmmmm
Modbus Register Types
Parameter Access (R43,998 – R46,999)
Parameter values are given as integers in the range of registers from R44,000 to R44,999.
The last three numbers of the register correspond to the parameter number.
Usually, the parameters are all read / write.
Each parameter register has a corresponding format register that holds the format
information required to interpret the value. See
Format Words (R46,000 to R46,999)
on
page 105.
Parameter Indexing
Many parameters are indexed. There are two possible indexes: a primary index and a
secondary index. A secondary index is a sub-address of the primary index. Some indexed
parameters affect multiple I/O devices.
The following is an example of a primary index:
P111 is the Relay Control Function. This parameter determines how a relay is controlled
by the MultiRanger (used as an alarm, for pump control, etc.). Because there are up to six
relays on the MultiRanger, P111 is indexed by six to allow each relay to be programmed
independently.
A few parameters also have a secondary index. While a secondary index is important for
setting up the MultiRanger, it is almost never needed through remote communications.
Indexing the Parameter Access Area
Each parameter communicates its value to only one register. You must know the index(es)
for the parameter in order to interpret the information in the register correctly.
For example, to make use of the value returned in register R44,111 you must know which
relay it is referring to. See
Relay Function Codes (P111 Only)
on page 110 for details on
P111 values.
To determine the index values, the primary and secondary index must be read or write.
The two possible methods of handling these index values are described in the following
paragraphs:
Global Index Method
and
Parameter Specific Index Method
.
Parameter Register # Format Register # Parameter #
44,000 46,000 P000
44,001 46,001 P001
44,002 46002 P002
44,999 46,999 P999
Note:
Parameters P000 and P999 are read only. If P000 is set to lock activated then
all of the parameters are read only
Parameter P999 (Master Reset) cannot be used via Modbus
•See
Data Types
on page 107 for a description of the different types of data
associated with different parameters

Table of Contents

Other manuals for Siemens MAG 5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens MAG 5000 and is the answer not in the manual?

Siemens MAG 5000 Specifications

General IconGeneral
TypeElectromagnetic Flowmeter
Protection ClassIP67
MaterialStainless Steel, Carbon Steel
Power Supply24 V DC, 100-240 V AC
Accuracy±0.2% of flow rate
CommunicationHART, PROFIBUS, Modbus
Enclosure RatingIP67
Ambient Temperature Range-20°C to +60°C
SizesDN 2 to DN 3000
Lining MaterialsPTFE, Hard Rubber
Electrode MaterialsStainless Steel, Hastelloy, Tantalum
Process Temperature-40 to +180 °C (-40 to +356 °F) depending on liner
Process PressureUp to 40 bar (580 psi)
ApprovalsATEX, FM, CSA, IECEx
Flow Velocity Range0 to 12 m/s
Output Signals4-20 mA, Pulse, Frequency

Related product manuals