7ML19981FB05 MultiRanger 100/200 – INSTRUCTION MANUAL Page 13
mmmmm
Installation
MultiRanger Board
Installing the Battery
The battery (Rayovac BR2032) has a ten-year life expectancy. Please note the life
expectancy may be reduced by ambient temperature. If the unit loses external and
battery power, a capacitor will power the RAM for about ten minutes.
Installation Steps
1. Open the enclosure lid.
2. Slide the battery into the holder. Be sure to
align the + and – terminals correctly.
3. Close and secure enclosure lid.
Note: All parameter values are written to the EEPROM once every hour. The
battery is used to backup Standard Data Logging parameters (P300-P321)
between writes, in case of power failure.
L2/N L1
TB1
TB3
TB2
RELAY 1
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY 6
2
1
mA INPUT
SHIELD
SYNC
1
2
4 - 20 mA
OUTPUT S
TS-3
SHIELD
1
2
DISCRETE
INPUTS
RS485
B
A
COM
Battery
RS-232 RJ-11
Connector
Power Supply
Female Connector
for SmartLinx Card
SmartLinx Card
Te r mi n a ls
RS-485
Connections
Disconnect power before replacing the battery.