7ML19981FB05 MultiRanger 100/200 – INSTRUCTION MANUAL Page 157
mmmmm
Parameters
P310 Pump Hours
View or reset the accumulate ON time for the displayed Relay Number.
Value is displayed with a floating decimal point (the more figures displayed before the
decimal, the fewer displayed after). It is the value displayed when key is pressed in
the RUN mode.
P311 Pump Starts
View or reset the accumulated number of times the Relay Number has been ON.
This value is displayed when key is pressed and held for five seconds in RUN mode.
P312 Pump Run Ons [MR 200]
View or reset the accumulated number of times the displayed Relay Number has been
held ON via Run On Interval (P130).
Please note that this parameter applies to the MultiRanger 200 only.
Flow Records (P320 and P321) [MR 200]
Please note that these parameters apply to the MultiRanger 200 only.
These features are enabled if Operation is set for OCM (P001 = 6), or an OCM device is
defined (P600 0). Use them to identify the occurrence of the record high and low flow
rates as displayed in OCM Max Flow (P604) units, or as a percent of OCM Max Flow.
Press CLEAR keys to reset values once the installation is working correctly.
Primary Index Relay
Values Range: 0.000 to 9999
Related Relay Function (P111) set for any pump control feature
Primary Index Relay
Values Range: 0 to 9999
Related Relay Function (P111) set for any pump control feature
Primary Index Relay
Values Range: 0 to 9999
Related Relay Function (P111) set for any pump control feature