7ML19981FB05 MultiRanger 100/200 – INSTRUCTION MANUAL Page 149
mmmmm
Parameters
P210 0/4 mA Output Setpoint
Sets the process level corresponding to the 0 or 4mA value.
Enter the value (in applicable units or %) to correspond to 0 or 4 mA.
P211 20 mA Output Setpoint
Sets the process level that corresponds to the 20 mA value.
Enter the value (in applicable units or %) to correspond to 20 mA.
mA Output Limits (P212 and P213)
Use these features to adjust the minimum and/or maximum mA output values, which
should suit the input limit requirements of the external device.
P212 mA Output Min Limit
Sets the minimum mA output value (in mA) to be produced.
Preset is determined by mA Function (P200). If P200 = 1 or 3, then the preset is 0.0, or if
P200 = 2 or 4, then the preset is 3.8. For P200=1 or 3 (preset is 0.0), this parameter has no
effect because the minimum limit cannot be negative, and the minimum current is always
0.0 mA.
Primary Index mA output
Values Range: -999 to 9999
Related P211 20 mA Output Setpoint
Primary Index mA output
Values Range: -999 to 9999
Related P210 0/4 mA Output Setpoint
Primary Index mA output
Values
Range: 0.000 to 22.00
Preset: 0.0 or 3.8
Related
P200 mA Output Range
P213 mA Output Max Limit