Page 162 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB05
mmmmm
Parameters
P333 Auto Record Interval
Enter the time to elapse after an Auto Profile Record is saved before another Auto Profile
Record can be saved (subject to all other restrictions).
Auto Record ON and OFF Setpoints (P334 to P337)
Use Auto Record ON Setpoint (P334) and Auto Record OFF Setpoint (P335) to define the
boundaries within which the level must be, for the resultant Echo Profile to be considered
for an Auto Profile Record.
If ---- is displayed for either P334 or P335, Auto Profile Records are saved regardless of
current level (subject to all other restrictions).
Enter the level value in Units (P005) or percent of Span (P007) as referenced to
Empty (P006).
P334 Auto Record ON Setpoint
Enter the critical level which, in conjunction with Auto Record OFF Setpoint, defines the
boundaries for Auto Profile Records to be saved.
P335 Auto Record OFF Setpoint
Enter the critical level which, in conjunction with Auto Record ON Setpoint, defines the
boundaries for Auto Profile Records to be saved.
Primary Index Global
Values
Range: 0.0 to 9999 (minutes)
Preset: 120
Primary Index Global
Values Range: -999 to 9999
Related
P335 Auto Record OFF Setpoint
P336 Auto Record Filling / Emptying
P337 Auto Record LOE Time
Primary Index Global
Values Range: -999 to 9999
Related
P334 Auto Record ON Setpoint
P336 Auto Record Filling / Emptying
P337 Auto Record LOE Time