7ML19981FB05 MultiRanger 100/200 – INSTRUCTION MANUAL Page 15
mmmmm
Wiring
Wiring
Please note:
Verify that all system components are installed in accordance with instructions.
Connect all cable shields to the MultiRanger Shield Terminals. Avoid differential
ground potentials by not connecting cable shields to ground (earth) anywhere.
Keep exposed conductors on shielded cables as short as possible to reduce noise
on the line caused by stray transmissions and noise pickup.
Siemens Milltronics
Transducer(s)
Laptop running
Dolphin Plus
Customer Alarm,
Pump, or Control
Device
Siemens Milltronics
TS-3 Temperature
Sensor
Customer Device,
digital output
Customer Device,
analog output
Customer Network or
Modem
SmartLinx Card
Display, PLC, Chart
recorder, or other
Control Device
MultiRanger

Table of Contents

Other manuals for Siemens MAG 5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens MAG 5000 and is the answer not in the manual?

Siemens MAG 5000 Specifications

General IconGeneral
TypeElectromagnetic Flowmeter
Protection ClassIP67
MaterialStainless Steel, Carbon Steel
Power Supply24 V DC, 100-240 V AC
Accuracy±0.2% of flow rate
CommunicationHART, PROFIBUS, Modbus
Enclosure RatingIP67
Ambient Temperature Range-20°C to +60°C
SizesDN 2 to DN 3000
Lining MaterialsPTFE, Hard Rubber
Electrode MaterialsStainless Steel, Hastelloy, Tantalum
Process Temperature-40 to +180 °C (-40 to +356 °F) depending on liner
Process PressureUp to 40 bar (580 psi)
ApprovalsATEX, FM, CSA, IECEx
Flow Velocity Range0 to 12 m/s
Output Signals4-20 mA, Pulse, Frequency