7ML19981FB05 MultiRanger 100/200 – INSTRUCTION MANUAL Page 59
mmmmm
Pump Control
Set the Common Parameters
Prerequisite: Substitute the details of your application in place of the sample values
provided. If you are bench testing the unit, set your test values to be the same as the
sample values.
Set Relays to ALTERNATE DUTY ASSIST
Set the Relay ON Setpoints
Set the Relay OFF Setpoints
For more information, see
Appendix D: Pump Control Reference
on page 239.
Parameter
Index
1
1.
Example assumes a single measurement unit. If your MultiRanger has
dual point software installed, some parameters are indexed by two.
Value Description
P001 G 1 Operation = level
P002 G 1 Material = liquid
P003 G 2 Maximum Process Speed = medium
P004 G 102 Transducer = XPS-10
P005 G 1 Units = meters
P006 G 1.8 Empty = 1.8m
P007 G 1.4 Span = 1.4m
Parameter Index Value Description
P111 1 52
Sets the pump relays (index 1, 2, and 3) to
ALTERNATE DUTY ASSIST.
P111 2 52
P111 3 52
Parameter Index Value Description
P112 1 0.4m Sets the three setpoints for the pump relays.
The first cycle will use these setpoints.
Subsequent cycles rotate the setpoints
among the pumps.
P112 2 0.3m
P112 3 0.2m
Parameter Index Value Description
P113 0 1.3m By using index 0 all six relays are set at the
same time, including any alarm relays. Use
with caution.