Page 244 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB05
mmmmm
Appendix D: Pump Control
Pump Run-On (P130, P131)
Extends the RUN period for a pump based on the number of pump starts. This allows for
the wet well to be pumped lower than usual and reduces sludge build-up on the well
bottom.
Wall Cling Reduction (P136)
Varies the ON and OFF setpoints to keep a fat ring from forming around the walls of the
wet well.
Pump Group (P137)
Allows for two different Alternate Duty Assist or Alternate Duty Backup pump groups in
the same application.
Flush Device (P170 to P173)
Operates a flush valve or special flush device based on the number of pump starts,
usually to aerate wet well wastewater.