7ML19981FB05 MultiRanger 100/200 – INSTRUCTION MANUAL Page 253
mmmmm
Appendix H: Software Rev.
1.08 11/11/2004
• Improvements made as a result of Siemens
systems testing:
• PDM related: TVT display improvement to
prevent it from going negative. MLFB number
includes SMPI as well as Siemens
numbering. Change of some enumerations in
the Device Description.
• Device related: mA output no longer resets
when PAR_MA_FUNCTION (P201) is written
to. mA trims (P214, P215) now have the
property no Reset.
• Enhancement: Device Identification
command allows Tag, Description, Message,
and Date.
1.09 11/28/2005
• Correction for manual Shaper TVT shift due
to change in velocity.
• Resolved issue of reading some floats as
decimal shifted integers.
• The submergence algorithm now
implemented with the thresholds defined.
• Changes to support single DUART.
1.10 not released
1.11 04/20/2006
• Software modified to support replacement
component.
• Supports SIMATIC PDM version 6.02.
• Added support for true First echo processing
algorithm
Soft-
ware
Rev.
Date Changes