Power Modules
4.2 Blocksize Power Modules (PM240-2)
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
113
Line voltage 3-phase 380 … 480 VAC ± 10%
Order number
without integrated line filter
with integrated line filter
6SL3210–
1PE16-1UL1
1PE16-1AL1
6SL3210–
1PE18-0UL1
1PE18-0AL1
6SL3211–
1PE18-0UL1
1PE18-0UL1
of the external
Ω ≥ 140 ≥ 140 ≥ 140
Max. cable length
to braking resistor
L1, L2, L3,
Screw-type terminals
cable cross-section: 1.5 … 2.5 mm
2
Tightening torque: 0,5 Nm
Motor connection U2, V2, W2
DC-link connection, connection for
braking resistor
DCP/R1, DCN, R2
3)
(without external options)
Without line filter
With line filter
kg
kg
1,4
1,5
1,4
1,5
1,7
1,8
Rated output of a typical standard induction motor at 400 V.
The input current dep
ends on the motor load and line impedance. The input currents apply for a load with the type rating
(based on I
rated
) for a line impedance corresponding to u
k
= 1%.
Max. motor cable length 50 m (shielded) for PM240-2 Power Modules with integrated line filter to maintain the limit
values of EN 61800-3 Category C2.
4)
Power loss in the cabinet: 0.02 kW. The remaining power loss is dissipated via the heat sink.
Table 4- 13 Technical data of the PM240-2, FSB (400 V)
Line voltage 3-phase 380 … 480 VAC ± 10%
Order number
without integrated line filter
with integrated line filter
6SL3210–
1PE21-1UL0
1PE21-1AL0
6SL3210–
1PE21-4UL0
1PE21-4AL0
6SL3210–
1PE21-8UL0
1PE21-8AL0
6SL3211–
1PE21-8UL0
1PE21-8AL0
Rated current I
n
Base-load current I
H
for S6 operation (40%) l
s6
A
A
A
10,2
7,7
11,2
13,2
10,2
14,5
18,0
13,2
19,8
18,0
13,2
19,8
1)
based on I
n
H
kW
kW
4,0
3,0
5,5
4,0
7,5
5,5
7,5
5,5
4)