Parameter
Description Data Read/write
P026*
CouplCh fix
26
Service parameter, only for Siemens service personnel
Coupling between DSP<->C167
Important: Pilot version - changes probable
For experts only; not a parameter for general use!
This parameter is used for manually assigning a
connector (PWE) to a coupling channel (index). PWE = 0
signifies that the coupling channel is assigned
automatically (on wiring a connector). If, in the case of
double-word connectors, only one coupling channel is
assigned, then the high word is linked. If the same double-
word connector is assigned twice in the same coupling
block (one block corresponds to a sequence of 8
channels, e.g. Index 01 to 08, Index 09 to 16, Index 17 to
24, etc.), the double word is fully coupled.
An entry is refused if the channel or connector is already
in use (through automatic coupling assignment). See r027
in this connection. During download this can result in
writing of the parameter being refused.
Indices: Index=Channel number
Channel 01-40: Coupling to T2 (= 4T0)
Channel 41-56: Coupling to T2 (= 4T0) reserved for
position controller
Channel 57-64: Coupling to T3 (= 8T0)
Channel 65-72: Coupling to T4 (= 16T0)
index1: 0
Min: 0
Max: 8046
Unit: -
Indices: 72
Type: O2
Menus:
- Parameter menu
- Board configuration
- Drive setting
- Upread/free access
- Power section definition
Changeable in:
- Power section definition
- Board configuration
- Drive setting
r027
AssignmtCoupCh
27
Service parameter, only for Siemens service personnel
The visualization parameter shows the assignments made
to coupling channels C167<->DSP. The parameter value
indicates the connector number.
Parameter values:
0: Coupling channel free
9999: Coupling channel occupied (by internal datum)
Indices: Index=channel number
Channels 01-40: Coupling to T2 (= 4TO)
Channels 41-56: Coupling to T2 (=4T0) reserved for
position controller
Channels 57-64: Coupling to T3 (= 8TO)
Channels 65-72: Coupling to T4 (= 16TO)
Index 73 to Index 75 show the number of free coupling
channels (DSP<->C167) of time slots T2 to T4.
Dec.Plc.: 0
Unit: -
Indices: 75
Type: O2
Menus:
- Parameter menu
- Board configuration
- Drive setting
- Upread/free access
- Power section definition
P030*
S.Disp Binec
30
BICO parameter for selecting binectors which are to be
shown in visualization parameter r031. The binector
numbers entered in the respective index are displayed in
the same index of parameter r031.
In function diagram:
30.1
index1: 0
Unit: -
Indices: 5
Type: L2 ,B
Menus:
- Parameter menu
+ General parameters
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
r031
Display Binector
31
Visualization parameter for displaying the binectors given
in P030. The binectors displayed in the respective index
have been selected in the same index of parameter P030.
In function diagram:
30.2
Dec.Plc.: 0
Unit: -
Indices: 5
Type: O2
Menus:
- Parameter menu
+ General parameters
- Upread/free access
3
Siemens AG 6SE7087-6QX70 (Edition AL)
SIMOVERT MASTERDRIVES Compendium Motion Control