Parameter
Description Data Read/write
P134*
Config.Resolver
134
Parameter for configuration of resolver evaluation
xxx0 = Pulse encoder simulation SBR2: 512 pulses per
revolution, one zero pulse (1)
xxx1 = Pulse encoder simulation SBR2: 1024 pulses
per revolution, one zero pulse.
A multipole resolver delivers several sine/cosine periods
per revolution, thus multiplying the number of pulses and
also the number of zero pulses by the number of pole
pairs of the resolver.
Init: 1
Unit: -
Indices: -
Type: L2
Menus:
- Parameter menu
+ Motor/encoder
+ Encoder data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P135*
SelExtEncDSP
135
Function parameter for selecting the external encoder
0 = automatic detection
3 = Encoder (sine/cosine encoder) (SBM2)
4 = Multiturn encoder (SSI encoder, EQN encoder) (SBM2)
Init: 0
Min: 0
Max: 7
Unit: -
Indices: -
Type: O2
Menus:
- Parameter menu
+ Motor/encoder
+ Encoder data
- Quick parameterization
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P136*
Encoder Pulse #
136
Function parameter for entering the number of pulses of
the encoder. The squared value which corresponds to the
number of pulses of the encoder is to be entered.
Special setting 0: Number of pulses in P144
Special setting 1: Without function!
(Number of pulses in P144
and actual value is inverted.
See description of P144.)
Pulse number Parameter
4 2
8 3
16 4
32 5
64 6
128 7
256 8
512 9
1024 10
2048 11 (preset value)
4096 12
8192 13
16384 14
Special setting:
2048 15
without evaluation of the zero pulse!
In function diagram 240
Init: 11
Min: 0
Max: 15
Unit: -
Indices: -
Type: O2
Menus:
- Parameter menu
+ Motor/encoder
+ Encoder data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P137*
Pulse ExtEncod
137
Function parameter for entering the encoder pulse
number for the external encoder (only with SBM2 board).
The maximum permissible entry value for the pulse
number is 16000.
Init: 2048
Min: 60
Max: 60000
Unit: -
Indices: -
Type: O2
Menus:
- Parameter menu
+ Motor/encoder
+ Encoder data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P138
Src Motor Temp
138
BICO parameter for selecting the connector from which
the motor temperature is to be read in. For this purpose,
parameter P131 (Select TmpSensor) must be assigned
with selection index 5 (coupling via SrcMotorTemp). In
function diagram 491.1
Init:
Unit: -
Indices: -
Type: L2 ,K
Menus:
- Parameter menu
+ Motor/encoder
+ Encoder data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
18
Siemens AG 6SE7087-6QX70 (Edition AL)
SIMOVERT MASTERDRIVES Compendium Motion Control