Parameter
Description Data Read/write
Indices 7 to 8: Specification as exponent to base 2
The signal periods are derived from the singleturn
resolution taking into account the pulse multiplication.
Example: ROQ424
Signal periods: 512 (P148.01 = 9)
Singleturn ser. SSI protocol: 4096 inc/rev.
=> ratio P148.07 = 3 (2^3 = 8)
4096 / 8 = 512
23
Siemens AG 6SE7087-6QX70 (Edition AL)
SIMOVERT MASTERDRIVES Compendium Motion Control