Parameter
Description Data Read/write
P211*
S.2 Rel PosReg
211
BICO parameter for selecting the binector from which the
2nd command for releasing the position controller is to be
read in.
index1: 104
Unit: -
Indices: 2
,BDS
Type: L2 ,B
Menus:
- Parameter menu
+ Control/gating unit
+ Position control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P212*
S.Ctrl Setp
212
BICO parameter for selecting the connector from which
the motor speed for the Control operating mode of the
position controller is to be read in.
index1: 311
Unit: -
Indices: 2
,BDS
Type: L2 ,K
,K
Menus:
- Parameter menu
+ Control/gating unit
+ Position control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P213*
S.Release Ctrl
213
BICO parameter for selecting the binector from which the
command for releasing the Control operating mode for the
position controller is to be read in.
index1: 305
Unit: -
Indices: 2
,BDS
Type: L2 ,B
Menus:
- Parameter menu
+ Control/gating unit
+ Position control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
r214
Pos Reg Output
214
Visualization parameter for displaying the speed setpoint
at the position controller output.
Dec.Plc.: 3
Unit: %
Indices: -
Type: I4
Menus:
- Parameter menu
+ Control/gating unit
+ Position control
- Upread/free access
P220*
S.n(set)
220
BICO parameter for selecting the connector from which
the setpoint for the speed controller is to be read in.
index1: 75
Unit: -
Indices: 2
,BDS
Type: L2 ,K
,K
Menus:
- Parameter menu
+ Control/gating unit
+ Speed control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P221
Smooth n(set)
221
Function parameter for entering the smoothing time
constant for the speed setpoint.
index1: 0,0
Min: 0,0
Max: 100,0
Unit: ms
Indices: 4
,FDS
Type: O2
Menus:
- Parameter menu
+ Control/gating unit
+ Speed control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P222*
S.n(act)
222
Input connector for the actual speed. BICO parameter for
selecting the connector from which the actual value for the
speed controller is to be read in.
Init: 91
Unit: -
Indices: -
Type: L2 ,K
,K
Menus:
- Parameter menu
+ Control/gating unit
+ Speed control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P223
Smooth n(act)
223
Function parameter for entering the smoothing time
constant for the actual speed.
Init: 0,0
Min: 0,0
Max: 100,0
Unit: ms
Indices: -
Type: O2
Menus:
- Parameter menu
+ Control/gating unit
+ Speed control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
37
Siemens AG 6SE7087-6QX70 (Edition AL)
SIMOVERT MASTERDRIVES Compendium Motion Control