Parameter
Description Data Read/write
P224*
S.1 n(set/act)
224
BICO parameter for selecting the connector from which
the 1st signal for calculating the difference (actual/setpoint
difference) for the speed controller is to be read in. The
connected signal is treated as a setpoint and added to the
other signals. Preferably, additional setpoints, pre-control
values or the droop (KK0157) are connected.
index1: 0
Unit: -
Indices: 2
,BDS
Type: L2 ,K
,K
Menus:
- Parameter menu
+ Control/gating unit
+ Speed control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P225*
S.2 n(set/act)
225
BICO parameter for selecting the connector from which
the 2nd signal for calculating the difference
(actual/setpoint difference) for the speed controller is to be
read in. The connected signal is treated as a setpoint and
added to the other signals.
index1: 150
Unit: -
Indices: 2
,BDS
Type: L2 ,K
,K
Menus:
- Parameter menu
+ Control/gating unit
+ Speed control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P226*
S.3 n(set/act)
226
BICO parameter for selecting the connector from which
the 3rd signal for calculating the difference
(actual/setpoint difference) for the speed controller is to be
read in. The connected signal is treated as an actual
value and subtracted from the other signals.
index1: 151
Unit: -
Indices: 2
,BDS
Type: L2 ,K
,K
Menus:
- Parameter menu
+ Control/gating unit
+ Speed control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P227*
S.4 n(set/act)
227
BICO parameter for selecting the connector from which
the 4th signal for calculating the difference
(actual/setpoint difference) for the speed controller is to be
read in. The connected signal is treated as an actual
value and subtracted from the other signals.
index1: 0
Unit: -
Indices: 2
,BDS
Type: L2 ,K
,K
Menus:
- Parameter menu
+ Control/gating unit
+ Speed control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P228*
S.n(Deviation)
228
BICO parameter for selecting the connector from which
the deviation (actual/setpoint difference) for the speed
controller is to be read in.
index1: 152
Unit: -
Indices: 2
,BDS
Type: L2 ,K
,K
Menus:
- Parameter menu
+ Control/gating unit
+ Speed control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
r229
n (Setp Smooth)
229
Visualization parameter for displaying the smoothed
speed setpoint.
Dec.Plc.: 2
Unit: 1/min
Indices: -
Type: I4
Menus:
- Parameter menu
+ Control/gating unit
+ Speed control
- Upread/free access
r230
n (ActV Smooth)
230
Visualization parameter for displaying the smoothed
speed actual value.
Dec.Plc.: 2
Unit: 1/min
Indices: -
Type: I4
Menus:
- Parameter menu
+ Control/gating unit
+ Speed control
- Upread/free access
P231
n(act)_filter
231
This filter option is switched off for a parameter value of 0.
A second-order Bessel low-pass filter is switched into the
actual speed value channel for values greater than 0.
The parameter value is the base frequency of the low-
pass. (Frequency in Hz).
index1: 0
Min: 0
Max: 500
Unit: -
Indices: 2
Type: O2
Menus:
- Parameter menu
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
38
Siemens AG 6SE7087-6QX70 (Edition AL)
SIMOVERT MASTERDRIVES Compendium Motion Control