EasyManua.ls Logo

Siemens simovert masterdrives - Page 981

Siemens simovert masterdrives
1547 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function diagram
87654321
fp_mc_190_e.vsd
Control word 2
MASTERDRIVES MC
08.01.02
-190 -
V2.5
Bit 17
Bit 18
Bit 19
Bit 20
Bit 21
Bit 22
Bit 23
Bit 24
Bit 25
Bit 26
Bit 27
Bit 28
Bit 29
Bit 30
Bit 31
Selection function data set bit 0
Meaning
Selection function data set bit 1
Reserve
Reserve
Select fixed setpoint bit 0
Select fixed setpoint bit 1
Reserve
1= Enable flying restart
3)
0=Flying restart disabled
1=Enable droop, speed controller
0=Droop, speed controller disabled
1=Enable speed controller
0=Speed controller disabled
0=External fault 2 (F036)
2)
1=No external fault 2
0=Master drive (speed control)
1=Slave drive (torque control)
0=External alarm 1 (A015)
1=No external alarm 1
0=External alarm 2 (A016)
1=No external alarm 2
0=No checkback, waiting time P600 active
1=Checkback main contactor
0=Select BICO data set 1
1=Select BICO data set 2
to data sets [540.5]
to data sets [540.5]
to fixed setpoints [290.7]
to fixed setpoints [290.7]
to speed control [360.7]
to speed control [360.2]
to speed control [360.7]
to sequence control 1)
to alarm processing
to sequence control 1)
to alarm processing
to sequence control 1)
Bit No.
Bit 16
to sequence control 1)
to alarm processing
to data sets [540.4]
The sequence control system is the
internal control system (software) for
implementing the drive status (r001).
1)
1
to sequence control 1)
Pre-assignment of the BICO parameters:
1. Binector valid for BICO data set 1
2. Binector valid for BICO data set 2
31 30
23 22
29 28
21 20
27 26
19 18
25 24
17 16
Display of r551 on the PMU
The fault signal is sent only if the drive
is ON (operating status
011)
2)
The "flying restart" function is not
implemented.
3)
B
P576.B (0/0)
Src FuncDSetBit0
B
P580.B (0/16)
Src FixSetp Bit0
B
P581.B (0/0)
Src FixSetp Bit1
B
P583.B (0/0)
Src Fly Release
B
P585.B (1/1)
Src n-Reg Rel
B
P586.B (1/1)
Src No ExtFault2
B
P587.B (0/0)
Src Master/Slave
B
P588.B (1/1)
Src No Ext Warn1
B
P590 (0)
Src BICO DSet
B
P591.B (0/0)
Src ContactorMsg
B
P589.B (1/1)
Src No Ext Warn2
Control Word 2
r551
K0031
Control Word 2
B
P577.B (0/0)
Src FuncDSetBit1
B
P584.B (0/0)
Src Droop Rel
B0099
No n-Reg Enable
n959.26 = 4
B0092 FDS Bit 0
B0093 FDS Bit 1

Table of Contents

Other manuals for Siemens simovert masterdrives

Related product manuals