Commissioning
4.6 Alternatively: Creating a project with a device configuration derived from the hardware
Commissioning with Startdrive
156 Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
Result
The topology of the drive unit is read out. Existing DRIVE-CLiQ interconnections are
transferred directly from the actual topology of the drive unit.
The "Device configuration detection" dialog opens.
Figure 4-61 Example: Device configuration detection - all components assigned
All components found in the actual topology of the drive unit are displayed in an overview
(for details, see Section "Device configuration detection (Page 42)"). The list shows all
components which could be assigned to a main component (e.g. infeed unit).
Components that are not automatically assigned to a main component during device
configuration detection are listed at "Non-assignable components". These components can
be manually assigned via drag-and-drop or via the shortcut menu of a main component.