Commissioning
4.7 Basic parameterization of the drive objects
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
171
Limitation on/off (p0784)
With the "Limitation" drop-down list, select whether the output value of the measuring socket
is to be restricted to the limit values of the characteristic curve for the required measuring
socket.
1. Select one of the following settings in the "Limitation" drop-down list of a measuring
socket:
Limitation On
If signals are output outside the permissible measuring range, the signal is limited to
4.98 V or to 0 V.
Limitation Off
The output of signals outside the permissible measuring range causes a signal
overflow. In the event of an overflow, the signal jumps from 0 V to 4.98 V or from 4.98
to 0 V.
Select signal source for T0, T1 and T2
The signal to be output via a measuring socket is specified by interconnecting a signal
source p0771[0...2].
Table 4- 3 Important measuring signals (examples):
r0060
CO: Speed setpoint before speed setpoint filter
r0063
CO: Actual speed value
r0069[0...2]
CO: Actual phase currents value
r0075
CO: Field-generating current setpoint
r0076 CO: Actual field-generating current value
r0077
CO: Torque-generating current setpoint
r0078
CO: Actual torque-generating current value
1. Select the signal sources whose signal is to be output via the measuring socket for the
respective measuring sockets T0, T1 and T2.