Loading...
Text of the message class Number ac‐
cording to
PROFIdriv
e
Diagnostics inter‐
face
Cause and remedy PN
(hex)
DS1
(dec)
External measured value/signal s
tate outside of the permis‐
sible range
A measured value/signal s
tate read in via the input area (digital/
analog/temperature) has assumed an inadmissible value/state.
Determine and check the relevant signal.
Check the set thresholds.
(16) 900F 15
Application/technology function faulted
The application/technological function
has exceeded a (set) limit
(position, speed, torque…).
Determine and check the relevant limit.
Check the setpoint speci󹪝ed by the higher-level controller.
(17) 9010 16
Error in the parameterization/con󹪝gur
ation/commissioning
sequence
An error has been identi󹪝ed in the parameterization or in a com‐
missioning procedure, or the parameterization does not match
the actual device con󹪝guration.
Determine the precise cause of the fault using the commis‐
sioning tool.
Adapt the parameterization or device con󹪝guration.
(18) 9011 17
General drive fault
Group fault.
Determine t
he precise cause of the fault using the commis‐
sioning tool.
(19) 9012 18
Auxiliary unit faulted
The monitoring of an auxiliary unit (incoming transf
ormer, cool‐
ing unit…) has identi󹪝ed an inadmissible state.
Determine the exact cause of the fault and check the device
involved.
(20) 9013 19
Message value
Provides information about the com
position of the fault/alarm value.
Example:
Message value: Component number: %1, fault cause: %2
In this example, the message value contains information about the component number and
cause of the fault. Entries %1 and %2 are placeholders. If the commissioning software is
connected to the converter, then these placeholders are populated with the appropriate
values.
Variant
Speci󹪝es the product variant in which the message exists. This information is not applicable if
an alarm is the same for all product variants.
System messages
11.3Faults and alarms
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
326 Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA

Table of Contents

Other manuals for Siemens SINAMICS S200

Related product manuals