F01014 Topology: Component property changed
Message class: Hardware/software error (1)
Message value: Component number: %1
Component: None
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: The properties of the component have fundamentally changed.
F
ault value (r0949, interpre
t hexadecimal):
Component number.
Remedy: - Carry out a restart, reload parameters.
F01015 Internal software error
Message class: Hardware/software error (1)
Message value: %1
Component: Control Unit (CU)
Response: OFF2
Acknowledgment: POWER ON
Cause: An internal software error has occurred.
F
ault value (r0949, interpre
t decimal):
Only for internal Siemens troubleshooting.
Remedy: - Carry out a POWER ON (switch-o/switch-on) for all components.
- U
pgrade rmware to later version.
- Contact Technical Support.
A01016 Firmware changed
Message class: Hardware/software error (1)
Message value: %1
Component: Control Unit (CU)
Response: NONE
Acknowledgment: NONE
Cause: At least one rm
ware le in
the directory was illegally changed on the non-volatile memory (memory card/device memory)
with respect to the version when shipped from the factory.
Alarm value (r2124, interpret decimal):
0: Checksum of one le is incorrect.
1: File missing.
2: File too many.
3: Incorrect rmware version.
4: Incorrect checksum of the backup le.
Remedy: Restore the delivery condition of the non-volatile memory for the rmware (memory car
d/device memory).
A01017 Component lists changed
Message class: Hardware/software error (1)
Message value: %1
Component: Control Unit (CU)
Response: NONE
Acknowledgment: NONE