Cause: Data backup is incomplete
The partially saved par
ameters are not loaded the next time the system runs up.
For the system to successfully power up, all of the parameters must have been completely backed up.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy: Save all parameters.
See also: p0977 (Save all paramet
ers)
F01033 Units changeover: Reference parameter value invalid
Message class: Error in the parameterization / con󹪝guration / commissioning procedure (18)
Mes
sage value: Parameter: %1
Component: None
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: When changing over the units to the referred representation type, it is not permissible for any of the required reference
par
ameters t
o be equal to 0.0
Fault value (r0949, parameter):
Reference parameter whose value is 0.0.
Remedy: Set the value of the reference parameter to a number di󹪜erent than 0.0.
See also: p0304, p0305, p2000, p2002, p2003
F01034 Units changeover: Calculation parameter values after reference value change unsuccessful
Message class: Error in the parameterization / con󹪝guration / commissioning procedure (18)
Mes
sage value: Parameter: %1
Component: None
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: The change of a reference parameter meant that for an involved parameter the selected value was not able to be re-
calculat
ed in the per unit represent
ation. The change was rejected and the original parameter value restored.
Fault value (r0949, parameter):
Parameter whose value was not able to be re-calculated.
See also: p0304, p0305, p2000, p2002, p2003
Remedy: - Select the value of the reference parameter such that the parameter involved can be calculated in the per unit
representation.
A01035 ACX: Parameter backup 󹪝le corrupted
Message clas
s: Hardware/software error (1)
Message value: %1
Component: Control Unit (CU)
Response: NONE
Acknowledgment: NONE
System messages
11.3Faults and alarms
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
334 Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA