Cause: When the converter runs up, no complete data set was found from the parameter backup les. The last time that the
parame
terization was saved, it was not completely carried out.
It is possible that the backup was interrupted by switching o or withdrawing the memory card.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
aa = 01 hex:
Power up was realized without data backup. The drive is in the factory setting.
aa = 02 hex:
The last available backup data record was loaded. The parameterization must be checked. It is recommended that the
parameterization is downloaded again.
dd, cc, bb:
Only for internal Siemens troubleshooting.
See also: p0977 (Save all parameters)
Remedy: - Download the project again using the commissioning tool.
- Retentively sa
ve parameters (save all parameters p0977 = 1)
See also: p0977 (Save all parameters)
F01036 Parameter backup le missing
Message class: Har
dware/software error (1)
Message value: %1
Component: Control Unit (CU)
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: When loading the device parameterization, a parameter backup le canno
t be found.
Remedy: If t
he project data are backed up using the commissioning tool, then the project must be downloaded again.
Retentively sa
ve parameters (save all parameters, p0977 = 1), as a consequence, parameter les are completely written
back to the non-volatile memory.
Note:
If the project data have not been backed up, then a new rst commissioning is required.
F01038 Loading the parameter backup le unsuccessful
Message class: Har
dware/software error (1)
Message value: %1
Component: Control Unit (CU)
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: An error has occurred when loading parameter backup les fr
om the non-volatile memory
.
Remedy: - If you have saved the project data using the commissioning tool, then download the project again. Retentively save the
data or set p0977 = 1. This means that the par
ameter les are again completely written to the non-volatile memory.
- Replace the memory card or the converter.
F01039 Writing to the parameter back-up le unsuccessful
Message class: Har
dware/software error (1)
Message value: %1
Component: Control Unit (CU)
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: Writing to at least one parameter backup le in t
he non-volatile memory was unsucces
sful.
- A parameter backup le has the "read only" le attribute and cannot be overwritten.
- There is not sucient free memory space available.
- The non-volatile memory is defective and cannot be written to.
System messages
11.3Faults and alarms
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA 335