Remedy: - Check the free memory space in the non-volatile memory.
- Replace the memory card or the con
verter.
F01040 Save parameter settings and carry out a POWER ON
Message class: Error in the parameterization / conguration / commissioning procedure (18)
Mes
sage value: -
Component: None
Response: OFF2
Acknowledgment: POWER ON
Cause: A parameter was changed, which means that it is necessary to save the parameters and reboot.
Remedy: - Back up parameters.
- Carr
y out a POWER ON (switch-o/switch-on) f
or all components.
Then:
- Upload the drive unit (commissioning tool).
F01041 Parameter save necessary
Message class: Error in the parameterization / conguration / commissioning procedure (18)
Mes
sage value: %1
Component: None
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: Defective or missing les w
ere detect
ed on the memory card when booting.
Fault value (r0949, interpret decimal):
1: Source le cannot be opened.
2: Source le cannot be read.
3: Target directory cannot be set up.
4. Target le cannot be set up/opened.
5. Target le cannot be written to.
Additional values:
Only for internal Siemens troubleshooting.
Remedy: - Save the parameters.
- Download the project again t
o the drive unit.
- Update the rmware
- If required, replace the converter and/or memory card.
F01042 Parameter error during project download
Message class: Error in the parameterization / conguration / commissioning procedure (18)
Mes
sage value: Parameter: %1, index: %2, fault cause: %3
Component: None
Response: OFF2
Acknowledgment: IMMEDIATELY
System messages
11.3Faults and alarms
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
336 Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA