Parameter: Range active
Default setting (_:107) Range active = false
If you do not activate the Range active parameter, the function assumes a range of -20 mA to +20 mA or
-10 V to +10 V. The setting of the range for the scaled value then assumes a usable range of -20 mA to +20
mA or -10 V to +10 V.
If you activate theRange active parameter, then 4 additional parametersUpper limit, Upper limit
- SensorLower limit, and Lower limit - Sensor appear.
Note that this setting is activated by either placing, or not placing the relevant check mark in DIGSI (see
Figure 6-52).
Parameter: Conversion factor
Default setting (_:104) Conversion factor = 1.00
With the parameterConversion factor you can set the conversion factor for the measuring transducer.
Parameter: Upper limit, Upper limit - Sensor, Lower limit and Lower limit - Sensor
With the following parameters, you set the scaling of the measuring variables. By that, you can scale in an
application-specific way:
Default setting Upper limit = 20.00 mA
Default setting Upper limit - Sensor = 1.00
Default setting Lower limit = -20.00 mA
Default setting Lower limit - Sensor = 1.00
With these setting parameters, you set the operating range of the measuring transducer as well as the conver-
sion of the values transmitted to the sensor values. Harmonize the operating range of the measuring trans-
ducer with the transmitter of the sensor. Using the free scalability of the system, you can meet different
requirements. The following figure shows the setting parameters in general terms.
Function-Group Types
6.5 Function-Group Type Analog Units
SIPROTEC 5, Fault Recorder, Manual 191
C53000-G5040-C018-5, Edition 11.2017

Table of Contents

Other manuals for Siemens SIPROTEC 5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 5 and is the answer not in the manual?

Siemens SIPROTEC 5 Specifications

General IconGeneral
SeriesSIPROTEC 5
Communication ProtocolsIEC 61850, DNP3, Modbus
CybersecurityRole-based access control, secure communication
Modular DesignYes
Hardware RedundancyOptional
Operating Temperature-25°C to +70°C
Digital InputsConfigurable, number depends on I/O modules
Digital OutputsConfigurable, number depends on I/O modules
Analog InputsConfigurable, number depends on I/O modules
Current Transformer InputsConfigurable, number depends on I/O modules
Voltage Transformer InputsConfigurable, number depends on I/O modules
Time SynchronizationIRIG-B, SNTP, PTP
Protection FunctionsOvercurrent, Differential, Distance, Over/Under Voltage, Frequency
Housing19-inch Rack Mount
DimensionsDepends on module configuration
WeightDepends on module configuration
Voltage Input24V DC, 48V DC, 110V DC, 125V DC, 220V DC, 250V DC