[sctimedg-220415, 1, en_US]
Figure 3-33 Time Information in DIGSI
For every time source, you see the following:
Last received time (with date)
Receipt time of the last received time telegram
Configured type of timer
Indication of timer outage or failure
Whether the device time is currently synchronized from the time source
The lower section displays the device time, which is continuously updated. If the internal device time and the
infeed time source were synchronous at the time of telegram receipt, both displayed times are identical.
i
i
NOTE
All times displayed (also the time source) take into consideration the local time settings (zone and daylight
saving time of the device) in the form of a numerical offset for UTC (universal time).
Settings
Addr.
Parameter C Setting Options Default Setting
Time sync.
_:102 Time sync.:Time source
1
none
IRIG-B
DCF77
PI
SNTP
IEC 60870-5-103
PROFIBUS DP
Modbus
DNP3
IEEE 1588
IEC 60870-5-104
none
_:103 Time sync.:Time source
1 port
port J
port F
port E
port P
port N
port G
3.4.4
System Functions
3.4 Date and Time Synchronization
SIPROTEC 5, Fault Recorder, Manual 85
C53000-G5040-C018-5, Edition 11.2017