Finally, load the configuration in the device.
Temperature Simulation without Sensors
Connect a resistor on the sensor terminals of the RTD unit. Using this resistor, simulate a constant tempera-
ture. The resistance value should be around 50 Ω to 200 Ω.
If you want to simulate a changeable temperature, connect an adjustable resistor of maximum 470 Ω instead
of a fixed resistor.
6.5.9.3
Function-Group Types
6.5 Function-Group Type Analog Units
SIPROTEC 5, Fault Recorder, Manual 211