Function-Group Type Recorder
Overview of Functions
The fault recorder has a flash memory in which records can be saved. The recording documents operations
within the power system and the way in which devices respond to them. You can read out records from the
device and analyze them subsequently using evaluation tools such as SIGRA or SICAM PQS/SICAM PQ Analyzer.
Structure of the Function Group
The Recorder function group consists of the following functionalities:
General function block
Fast-scan recorder function
Slow-scan recorder function
Continuous recorder function
Trend recorder function
The following figure shows the structure of the Recorder function group and its link to other function groups.
The function blocks are described in the following chapters.
[dwfg7ke8-161012-01.tif, 3, en_US]
Figure 7-19 Structure of the Recorder Function Group
The Recorder function group is a central device function. Both the recording criterion and the measured-value
and binary channels to be recorded are functionally preconfigured through the application templates. You are
able to individually adapt the configuration in DIGSI 5.
Interfaces with Measuring Points
The function group receives the required measured values via its interfaces with the measuring points.
If you are using an application template, the Voltage/current 1-phase function group is connected to the
measuring points 1-phase voltage and 1-phase current and the Voltage/current 3-phase function group is
connected to the measuring points 3-phase voltage and the 3-phase current, since these connections are
7.2
7.2.1
7.2.2
Fault Recorder
7.2 Function-Group Type Recorder
SIPROTEC 5, Fault Recorder, Manual 231
C53000-G5040-C018-5, Edition 11.2017

Table of Contents

Other manuals for Siemens SIPROTEC 5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 5 and is the answer not in the manual?

Siemens SIPROTEC 5 Specifications

General IconGeneral
SeriesSIPROTEC 5
Communication ProtocolsIEC 61850, DNP3, Modbus
CybersecurityRole-based access control, secure communication
Modular DesignYes
Hardware RedundancyOptional
Operating Temperature-25°C to +70°C
Digital InputsConfigurable, number depends on I/O modules
Digital OutputsConfigurable, number depends on I/O modules
Analog InputsConfigurable, number depends on I/O modules
Current Transformer InputsConfigurable, number depends on I/O modules
Voltage Transformer InputsConfigurable, number depends on I/O modules
Time SynchronizationIRIG-B, SNTP, PTP
Protection FunctionsOvercurrent, Differential, Distance, Over/Under Voltage, Frequency
Housing19-inch Rack Mount
DimensionsDepends on module configuration
WeightDepends on module configuration
Voltage Input24V DC, 48V DC, 110V DC, 125V DC, 220V DC, 250V DC

Related product manuals