EasyManuals Logo

Siemens SIPROTEC 5 User Manual

Siemens SIPROTEC 5
490 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #203 background imageLoading...
Page #203 background image
RTD Unit, Serial
Overview
The RTD unit serial function:
Communicates with an external RTD unit serial via the Slave Unit Protocol (SUP) and records the meas-
ured temperatures from the RTD unit
Provides the captured temperatures to the temperature supervision function
Monitors communication with the RTD unit
The RTD unit Serial function is set up structurally in the same manner as the RTD unit Ether. function. The
mode of operation is also identical (see 6.5.7.3 Communication with an RTD Unit ).
Application and Setting Notes
Parameter: Port
Default setting (_:2311:103) Port = F
With the Port parameter, you set the slot for the communication module that will be used for the connection
with an external RTD unit.
If you want to connect the external RTD box to an Ethernet plug-in module, set the parameter Port = Port
F , Port E, Port P, or plug-in module position.
Parameter: Channel number
Default setting (_:2311:105) Channel number = 1
A serial communication module optionally uses 2 channels. With the Channel number settings, you set the
channel number (1 or 2) through which the RTD unit is connected to the device. The communication module
inputs are labeled with the channel numbers.
Parameter: Slave address
Default setting (_:2311:106) Slave address = 1
Use the Slave address parameter to define the device address of the RTD unit. If only one RTD unit is
connected to the serial bus, the default value
1
can be used. The same device address has to be set on the RTD
unit. The device address is important for distinguishing among several RTD units connected to a serial bus. Set
a unique device address (for example 1, 2 and 3 when connecting 3 RTD units) for each RTD unit and the same
device address for the parameter Slave address in the 3 RTD unit serial functions.
The following settings and information table shows only 1 of the 12 sensors, as the setting possibilities of the
12 sensors do not differ.
Settings
Addr.
Parameter C Setting Options Default Setting
General
_:2311:103 General:Port
port F
port E
port P
port N
port J
port J
_:2311:105 General:Channel number 1 to 2 1
_:2311:106 General:Slave address 1 to 254 1
Sensor 1
_:11611:102 Sensor 1:Sensor type
Pt 100
Ni 100
Ni 120
Pt 100
6.5.8
6.5.8.1
6.5.8.2
6.5.8.3
Function-Group Types
6.5 Function-Group Type Analog Units
SIPROTEC 5, Fault Recorder, Manual 203
C53000-G5040-C018-5, Edition 11.2017

Table of Contents

Other manuals for Siemens SIPROTEC 5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 5 and is the answer not in the manual?

Siemens SIPROTEC 5 Specifications

General IconGeneral
SeriesSIPROTEC 5
Communication ProtocolsIEC 61850, DNP3, Modbus
CybersecurityRole-based access control, secure communication
Modular DesignYes
Hardware RedundancyOptional
Operating Temperature-25°C to +70°C
Digital InputsConfigurable, number depends on I/O modules
Digital OutputsConfigurable, number depends on I/O modules
Analog InputsConfigurable, number depends on I/O modules
Current Transformer InputsConfigurable, number depends on I/O modules
Voltage Transformer InputsConfigurable, number depends on I/O modules
Time SynchronizationIRIG-B, SNTP, PTP
Protection FunctionsOvercurrent, Differential, Distance, Over/Under Voltage, Frequency
Housing19-inch Rack Mount
DimensionsDepends on module configuration
WeightDepends on module configuration
Voltage Input24V DC, 48V DC, 110V DC, 125V DC, 220V DC, 250V DC

Related product manuals