Multi-layered security mechanisms in all links of the security chain
Self-monitoring routines for reliable localization and indication of device faults
Automatic logging of access attempts and safety-critical operations on the devices and systems
Analog Inputs
The measuring inputs transform the currents and voltages coming from the instrument transformers and
adapt them to the internal processing level of the device. A SIPROTEC 5 device has current and/or voltage
transmitters. The current inputs are therefore intended for the detection of phase currents and ground
current. The ground current can be detected sensitively using a core balance current transformer. In addition,
phase currents can be detected very sensitively for a particularly precise measurement.
The voltage inputs detect the measuring voltage of device functions requiring current and voltage measured
values.
The analog values are digitized in the internal microcomputer for data processing.
Binary Inputs and Outputs
The device receives information from the system or from other devices via the binary inputs and outputs. Indi-
cations are generated for the remote signaling of important events and states.
Front Elements
For devices with an integrated or detached operation panel, LEDs and an LC display on the front provide infor-
mation on the device function and report events, states, and measured values. In conjunction with the LC
display, the integrated keypad enables on-site operation of the device. All device information such as setting
parameters, operating and fault indications or measured values can be displayed, and setting parameters
changed.
USB Interface and Serial Interfaces
The USB interface in the front cover enables communication with a personal computer when using the DIGSI 5
operating program. As a result, the operation of all device functions is possible. Additional interfaces on the
back are used to realize various communication protocols.
Redundant Communication
SIPROTEC 5 devices maintain complete communication redundancy:
Multiple redundant communication interfaces
Redundant and independent protocols for control centers possible (such as IEC 61850, either single or
redundant)
Redundant time synchronization (such as IRIG-B and SNTP)
Power Supply
The individual functional units of the device are powered by an internal power supply. Brief interruptions in
the supply voltage, which can occur during short circuits in the system auxiliary voltage supply, are bridged by
capacitor storage (see also the Technical Data).
Introduction
1.2 Properties of SIPROTEC 5
22 SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017

Table of Contents

Other manuals for Siemens SIPROTEC 5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 5 and is the answer not in the manual?

Siemens SIPROTEC 5 Specifications

General IconGeneral
SeriesSIPROTEC 5
Communication ProtocolsIEC 61850, DNP3, Modbus
CybersecurityRole-based access control, secure communication
Modular DesignYes
Hardware RedundancyOptional
Operating Temperature-25°C to +70°C
Digital InputsConfigurable, number depends on I/O modules
Digital OutputsConfigurable, number depends on I/O modules
Analog InputsConfigurable, number depends on I/O modules
Current Transformer InputsConfigurable, number depends on I/O modules
Voltage Transformer InputsConfigurable, number depends on I/O modules
Time SynchronizationIRIG-B, SNTP, PTP
Protection FunctionsOvercurrent, Differential, Distance, Over/Under Voltage, Frequency
Housing19-inch Rack Mount
DimensionsDepends on module configuration
WeightDepends on module configuration
Voltage Input24V DC, 48V DC, 110V DC, 125V DC, 220V DC, 250V DC

Related product manuals