[sc-cfc-statistic, 1, en_US]
Figure 8-3 CFC Statistics
i
i
NOTE
The fast-event-triggered CFC charts have the highest priority and are processed before all other tasks. At
this level, a considerable smaller number of ticks are available than at all other tasks. It is recommended to
configure only very-high-priority logic functions at this task and to configure the other logic functions in
any other level.
i
i
NOTE
Empty CFC charts also consume system resources. Empty charts that are not required any more should be
deleted.
Supervision Functions
8.2 Resource-Consumption Supervision
366 SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017