The group-warning indication
(_:301) Group warning
is prerouted to an LED of the base module.
Alarm Handling Group Indication
The
Group indication
is exclusively for user-specific purposes. There is no internal device supervision
function that activates this indication. If the binary input signal
(_:505) >Group indication
is set, the
indication
(_:302) Group indication
becomes active and is recorded in the operational log. In the
delivery condition there is no further response of the device. If the binary input signal is reset, the signal
(_:
302) Group indication
drops out. Via a CFC chart, you can define when the binary input signal
(_:505)
>Group indication
is to be set.
Supervision Functions
8.9 Group Indications
410 SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017