Tolerance 0.3 % of the measured value in the above mentioned
measuring range
Frequency range (expanded) 40 Hz to 69 Hz at f
rated
= 50 Hz
50 Hz to 70 Hz at f
rated
= 60 Hz
Tolerance 0.5 % of the measured value in the above mentioned
measuring range
Reactive power Q var secondary
Measuring range
Voltage range
Current range
Frequency range
|cosφ| ≤ 0.984
(0.8 to 1.2) · V
rated
(0.1 to 2) · I
rated
49 Hz to 51 Hz at f
rated
= 50 Hz
59 Hz to 61 Hz at f
rated
= 60 Hz
Tolerance 1.0 % of the measured value in the above mentioned
measuring range
Frequency range (expanded) 40 Hz to 69 Hz at f
rated
= 50 Hz
50 Hz to 70 Hz at f
rated
= 60 Hz
Tolerance 1.5 % of the measured value in the above mentioned
measuring range
Apparent power S VA secondary
Measuring range
Voltage range
Current range
Frequency range
(0.01 to 2) · S
rated
(0.8 to 1.2) · V
rated
(0.01 to 2) · I
rated
49 Hz to 51 Hz at f
rated
= 50 Hz
59 Hz to 61 Hz at f
rated
= 60 Hz
Tolerance 0.3 % of the measured value in the above mentioned
measuring range
Frequency range (expanded) 40 Hz to 60 Hz at f
rated
= 50 Hz
50 Hz to 70 Hz at f
rated
= 60 Hz
Tolerance 0.5 % of the measured value in the above mentioned
measuring range
Frequency
Frequency f
Hz
Range f
rated
- 0.20 Hz < f
rated
+ 0.20 Hz
Tolerance ± 5 mHz in the V
rated
range
Range f
rated
- 3.00 Hz < f
rated
+ 3.00 Hz
Tolerance ± 10 mHz in the V
rated
range
Frequency range (expanded) 25 Hz to 80 Hz; operational measured values
10 Hz to 80 Hz; functional measured values, system
frequency
Tolerance 20 mHz in the range f
rated
± 10 % for rated values
Statistical Values of the Device
Device operating hours
h
Range 0 to 9999999 h
Tolerance 1 h
Technical Data
11.6 Operational Measured Values and Statistical Values
446 SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017

Table of Contents

Other manuals for Siemens SIPROTEC 5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 5 and is the answer not in the manual?

Siemens SIPROTEC 5 Specifications

General IconGeneral
SeriesSIPROTEC 5
Communication ProtocolsIEC 61850, DNP3, Modbus
CybersecurityRole-based access control, secure communication
Modular DesignYes
Hardware RedundancyOptional
Operating Temperature-25°C to +70°C
Digital InputsConfigurable, number depends on I/O modules
Digital OutputsConfigurable, number depends on I/O modules
Analog InputsConfigurable, number depends on I/O modules
Current Transformer InputsConfigurable, number depends on I/O modules
Voltage Transformer InputsConfigurable, number depends on I/O modules
Time SynchronizationIRIG-B, SNTP, PTP
Protection FunctionsOvercurrent, Differential, Distance, Over/Under Voltage, Frequency
Housing19-inch Rack Mount
DimensionsDepends on module configuration
WeightDepends on module configuration
Voltage Input24V DC, 48V DC, 110V DC, 125V DC, 220V DC, 250V DC