AS-Interface 3SU14
11.10 Configuring the AS-Interface
SIRIUS ACT 3SU1 pushbuttons and signaling devices
290 System Manual, 08/2018, A5E03457306020A/RS-AK/010
3SU1400-1EC10-.AA0 / 3SU1400-1EE20-.AA0 and 3SU1400-1EA10-.AA0 AS-Interface modules
with fail-safe digital inputs
Technical data
3SU1400-1EC10-.AA0
3SU1400-1EE20-.AA0
3SU1400-1EA10-.AA0
I
e
< 60 mA
U
e
26.5 V ... 31.6 V
SELV / PELV
PL
e
Cat.
4
SILCL
3
PFH [1/h]
< 4.5 x 10
-9
[1/h]
PFD
avg
< 5.0 x 10
-6
SFF
> 99 %
DC
avg
> 99 %
AS-i slave profile IO / ID / ID2