A.1.2.9 Parameters - Data set (index) 131
Data set (index) 131 (parameters)
Note
Bits that are not described in the tables below are reserved and should be ignored.
Table A- 22 Data set (index) 131 (parameters)
Byte.Bit Subindex Description Value
0.0 ... 15.7 1 ... 3 Reserved
16.0 … 16.7 4 Functional mode IO0 Functional mode:
Factory setting: [0x01]
[0x01] Static input
[0x02] Static output
[0x03] PWM output
[0x04] Dimming output
[0x05] Switching input
[0x06] Switching output
[0x07] Switch-on duration input
[0x08] Switch-on duration output
17.0 … 17.7 5 Functional mode IO1
18.0 … 18.7 6 Functional mode IO2
19.0 … 19.7 7 Functional mode IO3
20.0 … 20.7 8 Functional mode IO4
21.0 … 21.7 9 Functional mode IO5
22.0 … 22.7 10 Functional mode IO6
23.0 … 23.7 11 Functional mode IO7
24.0 … 24.1 12 Setting range Factory setting: [0x00]
[0x00] Individual: Individual setting of all
IOs
[0x01] Collective: All IOs according to IO 0
mode
[0x02] Groups: Group 1 according to IO 0
mode
Group 2 according to IO 4 mode
24.2 13 Reset process data Factory setting: [0x01]
[0x00] enabled
[0x01] disabled
25.0 … 25.7 14 PWM frequency output 0 Frequency:
Factory setting: 1 Hz
Minimum: 1 Hz
Maximum: 255 Hz
Increment: 1 Hz
26.0 … 26.7 15 PWM frequency output 1
27.0 … 27.7 16 PWM frequency output 2
28.0 … 28.7 17 PWM frequency output 3
29.0 … 29.7 18 PWM frequency output 4
30.0 … 30.7 19 PWM frequency output 5
31.0 … 31.7 20 PWM frequency output 6
32.0 … 32.7 21 PWM frequency output 7