AS-Interface 3SU14
11.11 Diagnosis of ASIsafe F adapters for front plate mounting
SIRIUS ACT 3SU1 pushbuttons and signaling devices
System Manual, 08/2018, A5E03457306020A/RS-AK/010
293
11.11
Diagnosis of ASIsafe F adapters for front plate mounting
Status display
The status of a module is indicated by LEDs with continuous or flashing light. This enables
diagnostics at a glance:
For AS-i communication via a dual LED
For the switching state of the inputs with yellow LEDs
The following chapters provide an overview of the LED status displays of the AS-i modules.
Inputs
Each input has a yellow LED with designation "F-INx". For the functions, see the table below:
Table 11- 1 Diagnostics of the inputs via LED
F-IN x
Meaning
Yellow
Signal activated
OFF Signal deactivated
Status display AS-i / FAULT
All modules have a dual LED (green/red) for the "AS-i / FAULT" status display. For the
functions and remedies, see the table below:
Table 11- 2 Diagnostics of the AS-i status via LEDs
AS-i / FAULT
(green / red)
Possible cause
Possible remedial measures
Green Normal operation,
AS-i communication OK
Red No AS-i communication:
Master is switched off or offline
Ensure AS-i communication:
Switch on the master or switch it to online
mode
Slave is not configured in the master Reconfigure the master
Incorrect slave type connected Connect the correct module
Slave has the wrong address Check/correct the slave address
Flashing
yellow/red
Module has slave address "0"
(delivery condition)
Assign an address other than "0"
OFF
No AS-i voltage
Switch on AS-i voltage
AS-i voltage has been connected with reverse
polarity
Connect it correctly
AS-i voltage too low
Measure the AS-i voltage (approx. 30 V DC)