AS-Interface 3SU14
11.10 Configuring the AS-Interface
SIRIUS ACT 3SU1 pushbuttons and signaling devices
292 System Manual, 08/2018, A5E03457306020A/RS-AK/010
3SU1401-2EE20-6AA0 and 3SU1400-2EA10-6AA0 AS-Interface modules with fail-safe digital inputs
Technical data
3SU1400-2EA10-6AA0
3SU1401-2EE20-6AA0
I
e
< 60 mA
U
e
18.0 V ... 31.6 V
PL e
Cat.
4
SILCL 3
PFH [1/h]
< 4.8 x 10
-9
[1/h]
PFD
avg
< 5.0 x 10
-6
SFF
> 99 %
DC
avg
> 99 %
AS-i slave profile IO / ID / ID2
(HEX)
0 / B / F 7 / B / 0
ID1 code (HEX)
1 ... F
1 ... F